MPI-530

Catalog index: WMGBMPI530

Multi-Function Meter Of Electrical System Parameters

Keep up to date with products in the category
  • Professional and versatile

    The multifunctional meter of parameters of electrical installations Sonel MPI-530 is used for precise measurements of electrical installations. The device has been constructed in compliance with the requirements of EN 61557 standard. It makes it possible to carry out all measurements connected with protection against electric shock described in the HD 60364-6 standard.

    The Sonel MPI-530 specialised meter is distinguished by extensive ground measurement functions - additional clamp methods and soil resistivity. Using the optional AuroISO-1000C adapter, automatic insulation resistance measurements are also possible in sockets and for 3-, 4- and 5-core cables.

    With the use of the Sonel MPI-530 meter it is also possible to test the illumination intensity. An additional external probe is required for this purpose. The instrument can record and analyse network parameters - including harmonics up to 40th. Another advantage of the meter is the robust IP54 casing, which protects the device from mechanical damage, dust or splashing.

    Features

    The meter offers a wide range of functionalities. It combines the measuring capabilities of several devices, while ensuring equally good accuracy.

    • MPI-530 can be used for all measurements for commissioning of electrical installations in accordance with applicable regulations:
      • short circuit loop impedance (also in circuits secured with RCDs),
      • RCD parameters, » insulation resistance,
      • earth resistance (4 measurement methods + soil resistivity measurement),
      • continuity of protective and equipotential bondings,
      • light intensity measurement,
      • phase sequence test, » motor rotation direction test.
    • MPI-530 can record 50/60 Hz power quality parameters:
      • voltage L1 – average values in the range up to 500 V,
      • L1 current – average values, current measurement in the range up to 3 kA (depending on the current probes used),
      • frequency in the range of 40 Hz – 70 Hz,
      • active (P), reactive (Q) and apparent (S) power,
      • power factor (PF), cosφ,
      • harmonics (up to 40th for voltage and current),
      • total harmonic distortion (THD) for current and voltage.

    Inspection of electrical safety

    This device may be used to inspect safety of electrical systems in households and industrial facilities. Measurements can be easily automated with:

    • auto mode of residual current devices (RCD) tests,
    • the WS adapter that can be used for testing systems via standard 230 V sockets,
    • AutoISO-1000C adapter for automatic insulation resistance test of 3-, 4- and 5-conductor cables, without switching.

    Memory structure

    The memory structure has a tree form. It has the ability to store tens of thousands of results in the configuration of CLIENT-OBJECT-FACILITY-MEASURING POINT, which helps to create a clear test protocol during later stages. This structure may be prepared in the meter, before starting the work. Entering data into the device is facilitated by QWERTY keyboard with Bluetooth communication module.

    Built-in help system

    The device has built-in help screens with measurement diagrams. Thanks to this you can easily and quickly check and make sure how to connect to a given system depending on the type of performed measurement.

    Increased resistance to environmental conditions

    The MPI-530 meter will cope well in difficult environmental conditions. Protection against penetration of dust and water is ensured by a unique housing with a level of protection IP54. It is resistant to mechanical damage, and a special design allows you to easily protect the screen by shielding using the cover of the meter. In addition to the fact that it protects against damage, it also allows you to conveniently carry and use the device in different positions.

    Communication and software

    You can easily transfer measurement data to your computer via USB port or Bluetooth wireless communication. In order to generate a report on measurements for electric shock protection, use Sonel Reports PLUS software. Saving the downloaded data to the simplest formats and printing is provided by free Sonel Reader software

Specification

Measurement of short circuit loop impedance:

  • impedance measurement with resolution 0,001 Ω and 23 A current (44 A phase-to-phase) – short-circuit resistor RZW=10 Ω,
  • measurement range: 95…440 V, frequency 45…65 Hz,
  • measurement of short circuit loop impedance with resolution 0,01 Ω, in protected systems without tripping the RCD’s with IΔn ≥ 30 mA,
  • automatic calculation of short-circuit current, differentiating between phase-to-phase and phase-to-neutral voltage,
  • measurements using UNI-Schuko plug with measurement triggering  button (also when L and N leads are exchangeable) or 1,2 m, 5 m, 10 m, 20 m test leads, with optional use of  3-phase socket adapters (AGT),
  • selection of installation protections and automatic evaluation of measurements results.

Tests of residual current devices (RCD), types AC, A, F, B and B+:

  • measurement of general, short-time delay and selective RCD’s with rated residual current of 10, 30, 100, 300, 500 and 1000 mA,
  • automatic measurement of all RCD parameters (when the START button is pressed, the meter performs the whole measurement cycle, including the.

L-PE short circuit loop impedance measurement with 15 mA current),

  • user selected waveform of forced leakage current: sinusoidal (start from increasing or decreasing edge), unidirectional pulsating (positive or negative), unidirectional pulsating with DC bias (positive and negative), direct (positive and negative),
  • measurement of tripping current IA using the ramp current,
  • measurement of tripping time tA at  ½IΔn, 1IΔn, 2IΔn and 5IΔn ,
  • measurement of touch voltage UB and protective conductor resistance RE without the RCD tripping,
  • detection that L and N conductors are switched in the socket; will not affect the measurement,
  • measurement of tripping current  IA and actual tripping time tAI at single activation of RCD,
  • measurement for 95…270 V voltage.

Insulation resistance measurements:

  • test voltage values: 50 V, 100 V,  250 V,  500 V  and 1000 V,
  • insulation resistance measurements up to 10 GΩ,
  • in-socket measurements using the UNI-Schuko adapter,
  • meter is protected against voltage on the tested object and voltage appearing during the measurement,
  • auto-discharge of the object after the measurement,
  • automatic measurement of all resistance combinations in three-, four- and five core leads using the additional AutoISO-1000C adapter,
  • acoustic signalling of five-second periods to enable determining the time profile during the insulation resistance measurements.

Low-voltage resistance measurement of equipotential and protective bonding:

  • continuity measurement  of protective conductor with  ≥200 mA current in both directions,
  • low current measurement  with sound signal,
  • autocalibration of test leads – leads of any length can be used.

Earth resistance measurements:

  • measurement with 3- and 4-pole methods with 2 additional electrodes,
  • measurement with the 3-pole method with and additional clamp,
  • measurement with 2-clamp method.

Soil resistivity measurements.
Illuminance measurements.
Quick check of PE connection correctness.
Measurement and recording of voltage, frequency, AC, cosφ and power (active,reactive and apparent), voltage and current harmonics up to 40,  THD.
Checking reactive phase sequence and motor direction of rotation.
Innovative memory with possibility of description of: measurement points, facilities, names of customers.
Power supply from rechargeable of disposable batteries (optional)
The meter conforms to EN 61557.

Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L
Test current: 23/40 A; measuring range acc. to IEC 61557: 0,13…1999,9 Ω
(for 1.2 m test lead):

Display range Resolution Accuracy
0,000…19,999 Ω 0,001 Ω ±(5% m.v. + 0,03 Ω)
20,00…199,99 Ω 0,01 Ω ±(5% m.v. +0,3 Ω)
200,0…1999,9 Ω 0,1 Ω ±(5% m.v. + 3 Ω)

Rated voltage: 95…270 V (for ZL-PE and ZL-N) and 95…440 V (for ZL-L)
Frequency: 45…65 Hz;

Measurement of short circuit loop impedance ZL-PE in RCD mode
Test current: 15 mA, measuring range acc. to IEC 61557: 0,50…1999 Ω

Display range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(6% w.m. + 10 digits)
20,0…199,9 Ω 0,1 Ω ±(6% w.m. + 5 digits)
200…1999 Ω 1 Ω

Rated voltage: 95…270 V
Frequency: 45…65 Hz

Measurement of earth resistance RE with the 3p and 4p method
Measuring range acc. to IEC 61557 – 5:

  • 0,50 Ω…1,99 kΩ for test voltage 50 V
  • 0,56 Ω…1,99 kΩ for test voltage 25 V
Display range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits)
10,0…99,9 Ω 0,1 Ω ±(2% m.v.. + 3 digits)
100…999 Ω 1 Ω
1,00…1,99 kΩ 0,01 kΩ
  • test voltage: 25 V or 50 V rms
  • test current: 20 mA, sinusoidal rms 125 Hz (for fn=50 Hz) and 150 Hz (for fn=60 Hz)
  • measurement blocked at interference voltage UN > 24 V
  • maximum measured interference voltage Unmax= 100 V
  • maximum resistance of auxiliary earth electrodes 50 kΩ

Selective earth resistance measurement with clamp (3p + clamp)

Display range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(8% m.v. + 4 digits)
10,0…99,9 Ω 0,1 Ω
100…999 Ω 1 Ω
1,00…1,99 kΩ 0,01 kΩ
  • measurement with additional current clamp
  • interference current measuring range: up to 9,99 A

Selective earth measurement with two clamps

Display range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(10% m.v. + 4 digits)
10,0…99,9 Ω 0,1 Ω
100…999 Ω ±(20% m.v. + 4 digits)
  • measurement with transmitting and receiving clamps
  • interference current measuring range: up to 9,99 A

Soil resistivity mesurement (ρ)

Display range Resolution Accuracy
0,0…99,9 Ωm 0,1 Ωm Depending on accuracy
of RE measurement
100…999 Ωm 1 Ωm
1,00…9,99 Ωm 0,01 kΩm
10,0…99,9 kΩm 0,1 kΩm
  • measurement with Wenner’s method
  • distance settable in metres or feet
  • distance range: 1…30 m (1…90 feet)

Phase sequence indication

  • Phase sequence indication: conforming, non-conforming
  • Mains voltage range UL-L: 100…440 V (45…65 Hz)
  • Display of phase-to-phase voltage values

Measurements of RCD parameters (voltage range 95…270 V):
RCD tripping test and measurement of tripping time tA (for tA measurement function)

RCD type Current Range Resolution Accuracy
General and
short-time
delay
0,5*IΔn 0…300 ms 1 ms ± (2% m.v. + 2 digits)(for RCD with IΔn=10 mA
and 0,5xIΔn uncertainty:
±(2% m.v. + 3 digits)
1*IΔn
2*IΔn 0…150 ms
5*IΔn 0…40 ms
Selective 0,5*IΔn 0…500 ms
1*IΔn
2*IΔn 0…200 ms
5*IΔn 0…150 ms

accuracy of residual current application: for 0,5*IΔn:-8…0% for 1*IΔn, 2*IΔn, 5*IΔn: 0…8%

Measurement of RCD tripping current IA for sinusoidal residual current (AC type)

Rated
current
Meas. range Resolution Test current Accuracy
10 mA 3,3…10,0 mA 0,1 mA 0,3 x IΔ..1,0 x IΔ ± 5%IΔn
30 mA 9,0…30,0 mA
100 mA 33…100 mA 1 mA
300 mA 90…300 mA
500 mA 150…500 mA
1000 mA 330…1000 mA

The measurement can be started from positive or negative half-period of forced leakage current

Measurement of RCD tripping current IA for unidirectional residual current and unidirectional
with the 6 mA DC bias (type A)

Rated
current
Meas. range Resolution Test current Accuracy
10 mA 3,5…20,0 mA 0,1 mA 0,35 x IΔn..2,0 x IΔn ±10%IΔn
30 mA 10,5…42,0 mA 0,35 x IΔn..1,4 x IΔn
100 mA 35,0…140 mA 1 mA
300 mA 105…420 mA
500 mA 175…700 mA

Measurement for positive or negative half-periods of forced leakage current

Measurement of RCD tripping current IA for direct residual current (type B)

Rated
current
Meas. range Resolution Test current Accuracy
10 mA 2,0…20,0 mA 0,1 mA 0,4 x IΔn..2,0 x IΔn ±10%IΔn
30 mA 6…60 mA 1 mA
100 mA 20…200 mA
300 mA 60…600 mA
500 mA 100…1000 mA

Measurement for positive or negative half-periods of forced leakage current
IΔn – rated residual current

Insulation resistance measurements
Measuring range acc. to IEC 61557 – 2:

  • for UN = 50 V: 50 kΩ…250 MΩ
  • for U= 100 V: 100 kΩ…500 MΩ
  • for UN = 250 V: 250 kΩ…999 MΩ
  • for UN = 500 V: 500 kΩ…2 GΩ
  • for UN = 1000 V: 1,000 MΩ…9,99 GΩ
Display range*) Resolution Accuracy
0…1999 kΩ 1 kΩ ±(3% m.v. + 8 digits)
2,00…19,99 MΩ 0,01 MΩ
20,0…199,9 MΩ 0,1 MΩ
200…999 MΩ 1 MΩ
1,00…9,99 MΩ 0,01 GΩ ±(4% m.v. + 6 digits)

*) not greater than measuring range for given voltage

Low-voltage measurement of resistance and circuit continuity
Measurement of protective conductor continuity with the ±200 mA current

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…400 Ω 1 Ω
  • voltage on open terminals: 4…9 V
  • output current at R < 2 Ω: min. 200 mA
  • autocalibration of test leads
  • measurements for both current polarities

Illuminance measurement

Range Resolution Accuracy
0,1…99,9 lx 0,1 lx ±(5% m.v. + 2 digits)
100…999 lx 1 lx
1,00…9,99 klx 0,01 lx
10,0…19,9 klx 0,1 lx

– – measurement in luxes (lx) or feet-candles (fc)

 

ANALYSIS AND RECORDING OF SINGLE-PHASE SYSTEM

  • Voltage measurement ULN: 0…500 V
  • Frequency range of measured voltages: 45,0…65,0 Hz
  • Frequency measurement range for 50…500 V voltages: 45,0…65,0 Hz (basic uncertainty max. ± 0,1% m.v. + 1 digit)
  • cosφ measurement: 0,00…1,00 (resolution 0,01)
  • Measurement and recording in single-phase system

 

Current measurement (True RMS)

Clamps Range Resolution Accuracy*
C-3, C-6 0,0…99,9 mA 0,1 mA ±(5% m.v. + 3 digits)
100…999 mA 1 mA
C-3,C-6
F-1, F-2, F-3
1,00…9,99 A 0,01 A ±(5% m.v. + 5 digits)
(C-3, C-6)
±(0,1% In + 2 digits)
(F-1, F-2, F-3)
10,0…99,9 A 0,1 A
100…999 A 1 A
F-1, F-2, F-3 1,00…3,00 kA 0,01 kA

* the accuracy of current clamps must also be taken into account

Measurement of active power P, reactive power Q, apparent power S and cosφ

Range
[W], [VA], [var]
Resolution
[W], [VA], [var]
Accuracy*
0…999 1 ±(7% m.v. + 3 digits)
1,00…9,99 k 0,01 k
10,0…99,9 k 0,1 k ±(7% m.v. + 5 digits)
100…999 k 1 k
1,00…1,50 M 0,01 M
  • voltage range: 0…500 V
  • current range: 0…1000 A (3000 A)
  • mains rated frequency fn: 50 Hz, 60 Hz

Voltage harmonics measurement

Range Resolution Nr harm. Accuracy
0,0…500 V 0,1 (1*) V 1,2,…15 ±(5% m.v. + 3 digits)
16,…40 ±(5% m.v. + 10 digits)
  • in addition display of h02…h40 values as percent of h01 (up to 999%)

*) from 300 V to 500 V

THD (in relation to the 1 st harmonics)

Resolution Accuracy
THD-F voltage
(h = 2…40)
0,0…999,9%
for URMS ≥ 1% Unom
0,1% ±5%
THD-F current
(h = 2…40)
0,0…999,9%
for IRMS ≥ 1% Inom
0,1% ±5%

 

NOTE: “m.v.” means “ measured value”

The instruments conforms to:

  • EN 61010 – 1 (general safety requirements)
  • EN 61010 – 031 (detailed safety requirements)
  • EN 61326 (electromagnetic compatibility)
  • EN 61557 – 10 (requirements for combined instruments)
  • IEC 60364 – 6-61 / HD 60364 – 6 (measurements – verification)
  • IEC 60364 – 4-41 / HD 60364 – 4-41 (measurements – protection against electric shock)
  • EN 04700 (measurements – acceptance tests)
  • EN 12464 (lighting of work places)
  • DIN VDE 0100
  • DIN VDE 0413
  • BS 7671