MRP-201
Catalog index: WMGBMRP201
RCD Meter
Specialist in residual current circuit breakers
The Sonel MRP-201 residual current circuit breaker meter is a specialist device for measuring all types of residual current circuit breakers - direct, short-delay, selective; types AC, A and B. It allows to measure tripping current, tripping time depending on differential current, resistance of protective conductor and contact voltage. Measurements can be performed individually or in series in automatic modes (all preset measurements for a given waveform or for all waveforms); simultaneous measurement of current and tripping time is also possible (with one RCD trip).
Features
- Testing RCD breakers of AC, A, B types
- Testing of general, short delay and selective RCDs for the rated current values 10, 15, 30, 100, 300, 500 mA
- Measurement of IA trip current and tripping time tA for currents 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
- RE and UB measurement without RCD tripping
- Extended AUTO function of RCD measurement
- Measurement of IA and tA during one RCD tripping
Additional functions
- Checking the correctness of PE connection using a contact electrode
- Measurement of voltage (0 … 500 V) and network frequency
- Memory of 990 results
- Wireless data transmission to a computer
- Backlit keypad
Application areas
The meter enables the user to measure the parameters of residual-current devices (RCDs), such as time or operating current. The device is useful for testing electrical systems with circuits protected by RCDs of AC, A and B type.
Increased resistance to environmental conditions
The meter will cope well in difficult environmental conditions. Protection against penetration of dust and water is ensured by a unique housing with a level of protection IP67.
Communication and software
You can easily transfer measurement data to your computer via wireless communication. In order to generate a report on measurements for electric shock protection, use Sonel Reports PLUS software. Saving the downloaded data to the simplest formats and printing is provided by free Sonel Reader software.
Specification
RCD trigger test and response time measurement tA
Measurement range according to IEC 61557: 0 ms…the upper limit of the displayed value
RCD type | Rated Current Multiplication Factor |
Range | Resolution | Accuracy |
General or short delay |
0,5*IΔn | 0…300 ms | 1 ms | ±(2% m.v. + 2 digits)* |
1*IΔn | ||||
2*IΔn | 0…150 ms | |||
5*IΔn | 0…40 ms | |||
Selective | 0,5*IΔn | 0…500 ms | ||
1*IΔn | ||||
2*IΔn | 0…200 ms | |||
5*IΔn | 0…150 ms |
*for IΔn= 10 mA and 0,5 IΔn accuracy is ±2% m.v. + 3 digits
- residual current setting accuracy:
– for 1*IΔn, 2*IΔn and 5*IΔn: 0…8%,
– for 0,5*IΔn : -8…0%, - nominal voltage Un: 220 V, 230 V, 240 V,
- work voltage range: 180…270 V,
- nominal frequency fn: 50 Hz, 60 Hz,
- work frequency range: 45 Hz…65 Hz.
RCD disconnecting current measurement for a sine AC test current (IA)
Measurement range according to IEC 61557: (0,3…1,0)IΔn
Selected rated RCD current |
Range | Resolution | Measurement current |
Accuracy |
10 mA | 3,3…10,0 mA | 0,1 mA | 0,3 mA x IΔn …1,0 mA x IΔn |
±5% IΔn |
30 mA | 9,0…30,0 mA | |||
100 mA | 33…100 mA | 1 mA | ||
300 mA | 90…300 mA | |||
500 mA | 150…500 mA |
- start of measurement from the positive or negative half sine period of the test current
- test current flow time – max. 7510 ms at f=50,0 Hz.
RCD disconnecting current measurement for unidirectional pulsed residual current and unidirectional pulsed current with a 6 mA DC offset (IA)
Measurement range according to IEC61557: (0,15…1,4) IΔn for IΔn > 30 mA and (0,15…2)IΔn for IΔn=10 mA
Selected rated RCD current |
Range | Resolution | Measurement current |
Accuracy |
10 mA | 1,5…20,0 mA | 0,1 mA | 0,15 x IΔn …2,0 mA x IΔn |
±10% IΔn |
30 mA | 4,5…42,0 mA | |||
100 mA | 15…140 mA | 1 mA | 0,15 mA x IΔn …1,4 mA x IΔn |
±10% IΔn |
300 mA | 45…420 mA |
- start of the measurement from the positive or negative half sine period of the test current
- test current flow time – max. 14710 ms at f=50 Hz
RCD response time measurement for the residual DC current (IA)
Measurement range according to IEC61557: (0,2…2)IΔn
Selected rated RCD current |
Range | Resolution | Measurement current |
Accuracy |
10 mA | 2…20,0 mA | 0,1 mA | 0.2 mA x IΔn …2,0 mA x IΔn |
±10% IΔn |
30 mA | 6…60 mA | 1 mA | ||
100 mA | 20…200 mA | |||
300 mA | 60…600 mA |
- measurement possible for positive or negative residual current
- test current flow time – max. 4500 ms at f=50 Hz
IΔn – rated residual current value RCD
Touch voltage measurement referred to the rated residual current (UB)
Measurement range according to IEC61557: 10,0…99,9 V
Range | Resolution | Measurement current | Accuracy |
0…9,9 V | 0,1 | 0,4 x IΔn | 0…10% IΔn m.v. ± 5 digits |
10,0…99,9 V | 0…15% IΔn m.v. |
Earthing resistance measurement (RE)
Selected rated RCD current |
Range | Resolution | Measurement current |
Accuracy |
10 mA | 0,01…5,00 kΩ | 0,01 kΩ | 4 mA | 0…+10% m.v. ± 5 digits |
30 mA | 0,01…1,66 kΩ | 12 mA | 0…+10% m.v. ± 5 digits | |
100 mA | 1…5000 Ω | 1 Ω | 40 mA | 0…+5%m.v. ± 5 digits |
300 mA | 1…166 Ω | 120 mA | ||
500 mA | 1…100 Ω | 200 mA |
Voltage measurement
Measurement range in accordance with IEC 61557: 1,1 Ω…1,99 kΩ
Range | Resolution | Accuracy |
0,00…299,9 V | 0,1 V | ±(2% m.v. + 6 digits) |
300…500 V | 1 V | ±(2% m.v. + 2 digits) |
- frequency range: 45…65 Hz
Range | Resolution | Accuracy |
45,0…65,0 Hz | 0,1 Hz | ±(0,1% m.v. + 1 digit) |
- voltage range 50…500 V
Electric security:
- type of insulation: double, according to EN 61010 – 1 and IEC 61557
- measurement category: CAT IV 300 V (III 600 V) acc. to EN 61010 – 1
- protection class: IP67
Other technical data:
- power supply: alkaline batteries LR6 (AA) (4 pcs.)
Rated operational conditions:
- operating temperature: -10…+50°C
- storing temperature: -20…70°C
- humidity: 20…80%
„m.v.” – measured value.
Reviews