HTD 6

HV-DC combi tester for cable core & sheath testing and fault converting 6kV

HV-DC combi tester for cable core & sheath testing and fault converting 6kV

The HTD 6 is a portable field test device for precise high voltage DC testing of various capacitive components in modern power networks. It is best suited for commissioning and routine tests on power cables. The instrument allows to perform cable core and cable sheath tests. In addition it provides a pulsed DC output to locate sheath faults in combination with a suitable ground fault sensor. Other available operating modes are burn converting & constant current testing. Thanks to the rugged instrument design and the integrated battery option this device can work in harsh environments. An extensive range of accessories complements the versatility of the test system

APPLICATIONS & FEATURES

  • Testing of cables in power, lighting, control and communication networks;
  • Testing electric heating cable systems;
  • Constant voltage and constant current supply;
  • Handy and simple to operate test combination;
  • Rugged (IP64) HV test set with precise and clearly visible analogue metering;
  • Adjustable current limitation;
  • High burn current (400mA) for fault conditioning;
  • Extensive range of accessories allows to upgrade to fault locating system;
  • Short circuit proof design.
  • Compact & Rugged Field Test Design
  • Portable with Integrated Battery Option
  • Constant Voltage and Constant Current Testing

ANALYSIS & TEST OF FAULTS

Max. test voltage (DC)                                    : 6kV

Max. test current (In)                                      : 12mA (2kV)

Resolution (accuracy)                                     : 100V / 1µA (± 1% FS)

Overcurrent trip                                              : 0,12mA to 12mA; switch-off

 

ISOLATION OF FAULTS

Fault conditioning (Imax)                               : 400mA

Pre-location (opt.)                                           : BFL 6 (extra HV bridge)

Pre-location (opt.)                                           : INTERFLEX 140 & ECF-C

 

 

MAPPING OF FAULTS

Max. output (DC)                                            : 6kV

Pulse rate (DC)                                                : 1:3

 

GENERAL DATA

Safety                                                              : built-in discharge unit

IP rating                                                          : IP64

Dimensions                                                     : 350 x 420 x 220mm

Weight                                                            : 9.5kg

Mains supply                                                   : 230V; 50H

Battery (opt.)                                                   : LiFePo4; 1,5hrs cont. operation

 

SCOPE OF SUPPLY

Test generator HTD 6 incl. connection cables (2m)

User manuals on CD

 

OPTIONS

Battery pack for HTD 6

Pinpointer Locator S with two earthing probes BFL 6 bridge type fault locator for pre-locating