The M32 is a minimised test and fault locating system for mobile integration with powerful extension options. It is built on the MX-platform that can integrate most modern test methods into an easy to operate and economic design without compromising safety or original measurement performance. The complete system and the plug-compatible extension modules are operated via central unified control unit. HV switching to test leads is semi-automatic and requires manual plug-over switching for high voltage testing and in case of multiple modules. Numerous additional available modules allow upgrading and customising the system to individual user requirements.
INTEGRATED MEASUREMENT FUNCTIONS
FEATURES
Safety features:
SPECIFIC CHARACTERISTICS | BASIC | OPTIONAL | |
Automatic HV Switch to Output | -1phase 32kV over HV cable for core integrated | -1phase 40kV over HV cable for locating | |
modules | modules combined with plug-over | ||
switching for additional modules | |||
ANALYSIS & QUALIFICATION OF FAULTS | |||
Insulation resistance measurement | -10kΩ to 3GΩ* | ||
HV withstand testing | -DC32kV (proof) | T | – DC40 or 80kV |
-Breakdown detection | VT* | – DC60/VLF40kV (cos) | |
VTD* – DC68/VLF48kV or DC90/64kV (sin) | |||
HV Test & Distance to Fault (SyncTest) | |||
Cable sheath testing | -DC10kV (proof) | -15kV DC; 300mA | |
ISOLATION & PRE-LOCATION OF FAULTS | |||
Integrated TDR Unit | -Measurement range: 95km (250km transient) | ||
-Measurement impulse: 160V; 50ns to 10µs | |||
-Impedance matching: 25 to 1600Ω | |||
Pre-location TDR-LV modes | -Direct 1ph over HV cable | -Direct 3ph over TDR cable | |
-Intermittent Fault Scanning | |||
Pre-location TDR-HV modes | -Arc Reflection Technology inductive (ARTi) | -Decay Voltage Coupling | |
-Surge Current Coupling | |||
Fault Conversion modes | -1A | ||
-25A @ 0 to 15kV | |||
-Monitored Fault Conversion (SyncTest) | |||
Sheath fault pre-location modes | -Bridge type fault locator 6kV | ||
MAPPING & PINPOINTING OF FAULTS | |||
Acoustic pinpointing in | -1000J @ 8/16/32kV | -2000 to 2500J @ 8/16/32kV | |
combination with Kamphone | -1000 to 2000J @ 4kV | ||
Sheath fault pinpointing in | -10kV; 50mA | -15kV; 300mA | |
combination with Locator S | |||
AF tracing and fault locating in | -10W; 512Hz to 200kHz | ||
combination with Tracer | -250W; 512Hz to 9,95kHz | ||
Mapping of trace and location | -GNSS sensor & software | ||
TESTING & DIAGNOSTICS | |||
Insulation resistance diagnostics | -PI, DAR,DD, SV and ramping | ||
HV testing & diagnostics | VTD -48kV rms, 1,6µF @ 0.1Hz (sin) | ||
VTD -64kV rms, 1µF @ 0.1Hz (sin) | |||
Partial discharge diagnostics & | VTD -0 to 64kVrms ; ± 1 x 10-4; MWT | ||
tan-delta diagnostics | (SyncTest) | ||
GENERAL DATA | |||
Connection assemblies | -25m (HV + LV) | -50m; 75m (HV + LV + TDR + BFL) | |
Power supply & consumption | -230V/50Hz; max. 2,5kVA | -230V/50Hz; max. 4kVA | |
Weight | -min. 260kg | -min. 620kg |