MZC-305
Catalog index: WMGBMZC305
Measurement of short circuit loop impedance (ZL-PE, ZL-N, ZL-L)
Measuring range according to IEC61557: 0,13…1999 Ω for 1,2 m test leads; 0,25…1999 Ω for UNI-SCHUKO adapter
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(5% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | ±(4% m.v.. + 3 digits) |
200…1999 Ω | 1 Ω |
Measurement of short circuit loop impedance ZL-PE RCD (without RCD tripping)
Measuring range according to IEC61557: 0,43…1999 Ω for 1,2 m test leads; 0,50…1999 Ω for UNI-SCHUKO adapter
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(6% m.v. + 10 digits) |
20,0…199,9 Ω | 0,1 Ω | ±(6% m.v. + 5 digits) |
200…1999 Ω | 1 Ω |
Voltage measurement
Range | Resolution | Accuracy |
0,0 V…249,9 V | 0,1 V | ±(2% m.v. + 4 digits) |
250 V…750 V | 1 V | ±(2% m.v. + 2 digits) |
Electrical safety:
Other technical data
Rated operational conditions:
The instrument meets the requirements of EMC standards