P-3  

Catalog index: WMGBP3

Voltage and continuity tester

 

      

P-3 can effectively check phase detection, and could be used for resistance measurement & circuit continuity tests.

P-3 Voltage and continuity tester functionality includes:

  • AC/DC voltage measurement and indication
  • Resistance measurement and circuit continuity testing
  • Indication of phase rotation
  • Single pole testing for phase detection
  • RCD testing
  • Identification and adjustment of phase

AC/DC voltage measurement and indication:

  • on LED bargraf for values: 12, 24, 50, 120, 230, 400, 690 V (indication of voltage with and without batteries),
  • display of measurement result in the LCD screen,
  • determination of voltage: alternating or polarisation of constant voltage.

Resistance measurement and circuit continuity test:

  • display of measurement result in the LCD screen,
  • signaling for resistance <400 kΩ.

Indicator of phase rotation:

  • indication of phase sequence for voltage >100 V.

Single pole test for phase detection:

  • indication by means of touch electrode,
  • optical and acoustic signaling for voltage >50 V.

RCD test:

  • RCD test IΔn ≤100 mA.

Identification and adjustment of phase:

  • phase determination at given socket referring to the other one,
  • possibility of phase determination at given socket with using additional transmitter – without time limit related to the synchronization of runs.

Terminals Ø2 mm/4 mm.

Illumination of measurement point.

DATA HOLD function, for holding measured values.

Meter meets the requirements of the standards EN 61010, IEC/EN 61243 – 3 EMC.

AC/DC voltage measurement

Range Resolution Accuracy
(AC)
Accuracy
(DC)
6,0…49,9 V 0,1 V ±(3% m.v. +4 digits) ±(3% m.v. + 3 digits)
50…750 V 1 V ±(2% m.v. +3 digits)

Resistance measurement

Range Resolution Accuracy
0…1999 Ω 1 Ω ±(3% m.v. + 8 digits)