PAT-805  

Catalog index: WMGBPAT805

Portable appliance tester

 

   

PAT-805 digital meter is used to measure the basic parameters of portable electrical equipment (power tools, white goods, etc.) which determine their safety: resistance of protective conductors, insulation resistance, continuity of connections, leakage current, power.

PAT-800 can be used to test the equipment performed in accordance with standards:

  • EN 60745 – 1 Hand-held motor-operated electric tools. Safety. General requirements
  • EN 61029 Safety of transportable motor-operated electric tools – General requirements
  • EN 60335 – 1 Household and similar electrical appliances -Safety -Part 1: General requirements
  • EN 60950 Safety of information technology equipment (IT Equipment)
  • VDE 0701 – 1 Instandsetzun, Änderung und Prüfung elektrischer Geräte. Teil 1: Allgemeine Anforderungen.
  • VDE 0702 Wiederholungsprüfungen an elektrischen Geräten

Basic functions:

  • measurement of protective conductor resistance with the currents: 200 mA, 10 A, 25 A (protection class I),
  • measurement of insulation resistance three measurement voltages: 100 V, 250 V and 500 V
  • measurement of equivalent leakage current,
  • measurement of PE leakage current,
  • measurement of residual leakage current,
  • measurement of touch leakage current,
  • measurement of equivalent leakage current,
  • measurement of power,
  • measurement of current consumption,
  • IEC lead test.

Other:

  • automatic measurement range selection,
  • 990 memory cells for measurement results with option of uploading to a PC through a USB port or printing,
  • professional software for data processing and reporting,
  • cooperation with a barcode reader and printer,
  • supports pendrive flash memory,
  • large and clear graphic display with backlight,
  • ergonomic operation.

Measurement of protective earth conductor resistance I=200 mA
(protection class I)

Display range Resolution Accuracy
0,00…0,99 Ω 0,01 Ω ±(4% m.v. + 2 digits)
1,00…19,99 Ω ±(4% m.v. + 3 digits)
  • test current: ≥200 mA for R= 0,2…1,99 Ω
  • upper limit adjustable in the 10 mΩ …1,99 Ω range with the 0,01 Ω resolution
  • measurement time adjustable in 1…60 s range, with the 1 s resolution

Measurement of protective earth conductor resistance I=10 A
(protection class I)

Display range Resolution Accuracy
0…999 mΩ 1 mΩ ±(3% m.v. + 4 digits)
1,00…1,99 Ω 0,01 Ω
  • technical method
  • test current: ≥10 A for R≤0,5 Ω
  • limit adjustable in the 10 mΩ …1,99 Ω range with the 0,01 Ω resolution
  • measurement time adjustable in 1…60 s range, with the 1 s resolution

Measurement of protective earth conductor resistance I=25 A
(protection class I)

Display range Resolution Accuracy
0…999 mΩ 1 mΩ ±(3% m.v. + 4 digits)
1,00…1,99 Ω 0,01 Ω
  • technical method
  • measurement with sinusoidal current of the mains frequency, test current: ≥25 A for R≤0,2 Ω
  • limit adjustable in the 10 mΩ …1,99 Ω range with the 0,01 Ω resolution
  • measurement time adjustable in 1…60 s range, with the 1 s resolution

Measurement of L-N circuit resistance

Display range Resolution Accuracy
0…999 mΩ 1 mΩ ±(5% m.v. + 5 digits)
1,00…4,99 Ω 0,01 Ω
  • test voltage: 4…8 V AC
  • short-circuit current: max. 5 mA

Measurement of insulation resistance
Measurement range according to IEC 61557 – 2 for:

  • UN=100 V: 100 kΩ…99,9 MΩ
  • UN=250 V: 250 kΩ…199,9 MΩ
  • UN=500 V: 500 kΩ…599,9 MΩ
UN Display range Resolution Accuracy
100 V 0…1999 kΩ 1 kΩ ±(5% m.v. + 8 digits)
2,0…19,99 MΩ 0,01 MΩ
20,0…99,9 MΩ 0,1 MΩ
250 V 0…1999 kΩ 1 kΩ
2,00…19,99 MΩ 0,01 MΩ
20,0…199,9 MΩ 0,1 MΩ
500 V 0…1999 kΩ 1 kΩ
2…19,99 MΩ 0,01 MΩ
20,0…599,9 MΩ 0,1 MΩ
  • limit adjustable in the: 0.01…9.9 mA range with the 0.1 MΩ resolution
  • adjustable measurement time: continuous measurement (Cont), or from 4 s to 3 min with 1 s resolution
  • automatic discharge of the capacity of the tested device after measurement
  • protection against measuring live devices
  • output current max. 1.4 mA

Measurement of PE and residual leakage current:

Display range Resolution Accuracy
0,00…3,99 mA 0,01 mA ±(5% m.v. + 2 digits)
4,0…19,9 mA 0,1 mA
  • limit adjustable in the 0.01…9.9 mA range with the 0.01 mA/0.1 mA resolution
  • adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
  • in the middle of the measurement time, the meter automatically switches the polarity at the measuring terminal and displays the greater value

Measurement of equivalent leakage current:

Display range Resolution Accuracy
0,00…3,99 mA 0,01 mA ±(5% m.v. + 2 digits)
4,0…19,9 mA 0,1 mA
  • limit adjustable in the 0.01…9.9 mA range with the 0.01 mA/0.1 mA resolution
  • adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
  • open circuit voltage 25…50 V

Measurement of touch leakage current:

Display range Resolution Accuracy
0,00…4,999 mA 0,001 mA ±(5% m.v. + 3 digits)
  • limit adjustable in the 0.01…9.9 mA range with the 0.01 mA/0.1 mA resolution
  • adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
  • current measurement band 20 Hz…100 kHz

Measurement of power S:

Display range Resolution Accuracy
0…999 VA 1 VA ±(5% m.v. + 3 digits)
1…3,99 kVA 0,01 kVA
  • adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution

Measurement of current consumption:

Display range Resolution Accuracy
0,00…15,99 A 0,01 A ±(2% m.v. + 3 digits)
  • adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution

Voltage measurement:

Display range Resolution Accuracy
187,0…265,0 V 0,01 V ±(2% m.v. + 2 digits)

„m.v.” measured value

Conforms to the EMC requirements according to EN 61326 – 1:2006 and EN 61326 – 2-2:2006.

Electrical safety:

  • insulation according to EN 61010 – 1 and IEC 61557
  • measurement category: II 300 V acc.to EN 61010 – 1
  • enclosure protection rating acc. to EN 60529: IP40

Other technical specification:

  • power supply: 187…265 V, 50 Hz
  • load current: max. 16 A (230 V)
  • measurement results memory: 990 cells
  • data transmission to PC: USB
  • dimensions: 330 x 235 x 120 mm
  • weight: about 4,75 kg
  • operating temperature: 0…+40°C
  • storage temperature: -20…+70°C
  • humidity: 20…80%

Data Sheet                                      

User Manual                                   

Declarations of conformity          

Firmware for PAT-805                 

Related Products