Measure insulation resistance up to 2 TΩ
The functional insulation resistance meter Sonel MIC-2511 allows you to measure insulation resistance with a test voltage of up to 2500 V. It surprises with numerous functions hidden in a neat and handy form. Due to its parameters, robust housing with IP65 protection level, low energy consumption from batteries and the possibility of recharging during measurements, the meter is a reliable tool that can be used in many areas. It is perfect for controlling industrial installations and traction networks, it is also successfully used in residential construction. The advantages of this device are especially appreciated by electricians working in maintenance, testing motors, cables and street lighting. The Sonel MIC-2511 meter is also useful for measurements during the construction and maintenance of photovoltaic installations. It is a reliable solution created for the needs of telecommunications network installers and heating network operators,
Characteristics
Additional features
Application
Insulation resistance meter with a wide range of applications. It works great both in housing construction, as well as when checking industrial installations or transmission and traction networks. Due to its features – excellent parameters, low energy consumption from the batteries and the possibility of recharging them during measurements, portability and a high degree of tightness of the housing – it is willingly used by electricians working in maintenance, testing motors, cables, street lighting or in construction and maintenance of photovoltaic installations. It perfectly meets the needs of telecommunications network installers and heating network operators, where it is required to control the alarm system of pre-insulated pipes.
Distinguishing features
The meter allows you to measure insulation resistance with a test voltage of up to 2500 V. In the case of testing cables, it automatically discharges their capacitance at the end of the measurement. Together with the PRZ-2 , i.e. a set for measuring resistance in ESD protected zones , it is a comprehensive tool for coordinators dealing with the protection of plants against static electricity.
Thanks to the device, you can control home and industrial electrical installations in terms of safety. Measurements can be easily automated by using the AutoISO-2511 adapter to test the insulation resistance of 3-, 4- and 5-core cables.
MIC-2511 will allow the user to measure the continuity of protective and equipotential bonding with a current greater than 200 mA, in both directions. The meter has a built-in voltmeter for DC and AC voltages up to 1500 V.
The extensive memory of the device allows you to save and send to the computer nearly 10,000 measurement results.
Built-in help system
The device has built-in help screens with measurement diagrams. Thanks to this, it is easy and quick to check how to connect a given system depending on the type of measurement performed.
Communications and software
Measurement data can be transferred to a computer via the USB port. In order to generate a test report in the field of electric shock protection, the Sonel Electrical Measurements program should be used . Saving the downloaded resources to the simplest formats and printing is provided by Sonel Reader .
Insulation resistance measurement
Measuring range according to IEC 61557-2 for R ISOmin =U ISOnom /I ISOnom …≤ 2 TΩ (I ISO =1.6 mA)
Range | Resolution | Accuracy |
---|---|---|
0.0…999.9 kΩ | 0.1 kΩ | ±(3% in m + 20 digits) |
1.000…9.999 MΩ | 0.001 MΩ | ±(3% in m + 20 digits) |
10.00…99.99 MΩ | 0.01MΩ | ±(3% in m + 20 digits) |
100.0…999.9 MΩ | 0.1MΩ | ±(3% in m + 20 digits) |
1.000…9.999 GΩ | 0.001 GΩ | ±(3% in m + 20 digits) |
10.00…99.99 GΩ | 0.01GΩ | ±(3% in m + 20 digits) |
100.0…999.9 GΩ | 0.1GΩ | ±(3% in m + 20 digits) |
1,000…2,000 TΩ | 0.001TΩ | ±(3% in m + 20 digits) |
“wm” – measured value
Values of the measured resistance depending on the measuring voltage
Voltage U n | Measurement range |
---|---|
50V | 50 GΩ |
100V | 100 GΩ |
250V | 250 GΩ |
500V | 500 GΩ |
1000V | 1.00TΩ |
2500V | 2.00TΩ |
DC and AC voltage measurement
Range | Resolution | Accuracy |
---|---|---|
0…1500V | 1V | ±(3% wm + 2 digits) |
frequency range: 45…65 Hz
Capacitance measurement
Range | Resolution | Accuracy |
---|---|---|
0…999nF | 1nF | ±(5% wm + 5 digits) |
1.00…9.99 μF | 0.01μF | ±(5% wm + 5 digits) |
Measurement of the continuity of protective and equipotential bonding with a current of 200 mA
Measuring range according to IEC 61557-2: 0.10…999 Ω
Range | Resolution | Accuracy |
---|---|---|
0.00…19.99 ohms | 0.01Ω | ±(2% wm + 3 digits) |
20.0…199.9 ohms | 0.1Ω | ±(2% wm + 3 digits) |
200…999 Ohms | 1 ohms | ±(4% wm + 3 digits) |
Temperature measurement
Range | Resolution | Accuracy |
---|---|---|
-40.0…99.9°C | 0.1°C | ±(3% wm + 8 digits) |
-40.0…211.8°F | 0.1°F | ±(3% wm + 16 digits) |
Resistance measurement in EPA zones
Range | Resolution | Accuracy |
---|---|---|
for Un = 10V | ||
0.0…999.9 kΩ | 0.1 kΩ | ±(8% in m + 20 digits) |
1.0…9.999 MΩ | 0.001 MΩ | ±(8% in m + 20 digits) |
10.00…99.99 MΩ | 0.01MΩ | ±(8% in m + 20 digits) |
100.0…999.9 MΩ | 0.1MΩ | ±(8% in m + 20 digits) |
1.0…10.0 GΩ | 0.1GΩ | ±(8% in m + 20 digits) |
for U n = 100 V | ||
0.0…999.9 kΩ | 0.1 kΩ | ±(3% in m + 20 digits) |
1.000…9.999 MΩ | 0.001 MΩ | ±(3% in m + 20 digits) |
10.00…99.99 MΩ | 0.01MΩ | ±(3% in m + 20 digits) |
100.0…999.9 MΩ | 0.1MΩ | ±(3% in m + 20 digits) |
1,000…9,999 GΩ | 0.001 GΩ | ±(3% in m + 20 digits) |
10.00…99.99 GΩ | 0.01GΩ | ±(3% in m + 20 digits) |
100.0…200.0 GΩ | 0.1GΩ | ±(8% in m + 20 digits) |
for U n = 500 V | ||
0.0…999.9 kΩ | 0.1 kΩ | ±(3% in m + 20 digits) |
1.000…9.999 MΩ | 0.001 MΩ | ±(3% in m + 20 digits) |
10.00…99.99 MΩ | 0.01MΩ | ±(3% in m + 20 digits) |
100.0…999.9 MΩ | 0.1MΩ | ±(3% in m + 20 digits) |
1,000…9,999 GΩ | 0.001 GΩ | ±(3% in m + 20 digits) |
10.00…99.99 GΩ | 0.01GΩ | ±(3% in m + 20 digits) |
100.0…999.9 GΩ | 0.1GΩ | ±(8% in m + 20 digits) |
1000 GΩ | 1 GΩ | ±(8% in m + 20 digits) |