MPI-540 + EVSE-01

Catalog index: WMGBMPI540EVSE01

Multi-Function Meter Of Electrical System Parameters & Adapter

Keep up to date with products in the category

SONEL MPI-540 + SONEL EVSE-01 SET

1. Multi-function meter of electrical system parameters Sonel MPI-540

The Sonel MPI-540 multifunctional meter is intended for testing home and industrial electrical installations. The instrument can be used to carry out measurements, the results of which determine the safety status of the installation. In addition, the user is able to record the parameters of the electrical networks located at these sites. This makes it possible to control the quality of electricity, and to measure electric shock protection parameters, using a single universal device.

Significant automation of measurements is made possible by the function of testing residual current circuit breakers in Auto mode, as well as measurement sequences pre-programmed by the manufacturer (so-called self-tests), which can also be extended with own sequences. Automatic measurement of insulation resistance of 3-, 4- and 5-core cables will be carried out with the Sonel AutoISO-1000C adapter.

 

2. Adapter for testing vehicle charging stations Sonel EVSE-01

Sonel EVSE-01 adapter allows to perform comprehensive measurements of electric vehicle charging stations - quickly and in accordance with applicable regulations. Simulating the charging cable (proximity pilot line - PP) and vehicle connection status (control pilot line - CP), it will bring the station into different operating states. This will enable measurements in the field of electric shock protection: ZS fault loop impedance, RISO insulation resistance and checking the parameters of RCD residual current devices.

To facilitate diagnostics, one of the Sonel EVSE-01 sockets is provided with pulse width modulation signal (PWM).

Application

The Sonel EVSE-01 adapter enables measurements of AC electric vehicle charging stations with type 2 connector. Tests for 1-phase and 3-phase stations are available - both with and without ventilation.

Specification

Sonel MPI-540 | Specifications – electrical installation parameters

Measurement functions Measurement range Display range Resolution Accuracy
Fault loop impedance
Fault loop ZL-PE, ZL-N, ZL-L 0.13 Ω…1999.9 Ω acc. to IEC 61557 0.00 Ω…1999 Ω from 0.001 Ω ±(5% m.v. + 30 digits)
Fault loop ZL-PE in RCD mode from 0.50 Ω…1999 Ω acc. to IEC 61557 0.00 Ω…1999 Ω from 0.01 Ω from ±(6% m.v. + 5 digits)
Measurements of RCD parameters
RCD tripping test and measurement of tripping time tA measuring current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
general and short-time delay RCD 0 ms…300 ms 0 ms…300 ms 1 ms from ±(2% m.v. + 2 digits)
selective RCD 0 ms…500 ms 0 ms…500 ms 1 ms from ±(2% m.v. + 2 digits)
Measurement of RCD tripping current IA measuring current 0 0.2 IΔn…2.0 IΔn
for sinusoidal residual current (AC type) 3.3 mA…1000 mA 3.3 mA…1000 mA from 0.1 mA ±5% IΔn
for unidirectional residual current and unidirectional with the 6 mA DC bias (type A) 3.5 mA…700 mA 3.5 mA…700 mA from 0.1 mA ±10% IΔn
for direct residual current (type B) 2.0 mA…1000 mA 2.0 mA…1000 mA from 0.1 mA ±10% IΔn
Earth resistance
3- and 4-pole method from 0.50 Ω…1.99 kΩ acc. to IEC 61557-5 0.00 Ω…1,99 kΩ from 0.01 Ω from ±(2% m.v. + 3 digits)
3-pole + clamp method 0.00 Ω…1.99 kΩ 0.00 Ω…1.99 kΩ from 0.01 Ω from ±(2% m.v. + 4 digits)
2-Pole method 0.00 Ω…99.9 kΩ 0.00 Ω…99.9 kΩ from 0.01 Ω from ±(10% m.v. + 4 digits)
Resistance-to-earth 0.0 Ω m…99.9 kΩm 0.0 Ωm…99.9 kΩm from 0.1 Ωm Depending on accuracy of RE measurement
Insulation resistance
Measuring voltage 50 V 50 kΩ…250 MΩ acc. to IEC 61557-2 0 kΩ…250 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 100 V 100 kΩ…500 MΩ acc. to IEC 61557-2 0 kΩ…500 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 250 V 250 kΩ…999 MΩ acc. to IEC 61557-2 0 kΩ…999 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 500 V 500 kΩ…2.00 GΩ acc. to IEC 61557-2 0 kΩ…2.00 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 1000 V 1000 kΩ…9.99 GΩ acc. to IEC 61557-2 0 kΩ…9.99 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Resistance of protective conductors and equipotential bondings
Measurement of resistance of protective conductors and equipotential bondings with ±200 mA current 0.12 Ω…400 Ω acc. to IEC 61557-4 0.00 Ω…400 Ω from 0.01 Ω ±(2% m.v. + 3 digits)
Measurement of resistance with low current 0.0 Ω…1999 Ω 0.0 Ω…1999 Ω from 0.1 Ω ±(3% m.v. + 3 digits)
Light intensity
Measurement in luxes (lx) 0 lx…399.9 klx 0 lx…399.9 klx from 0.001 lx from ±(2% m.v. + 5 digits)
Measurement in feet-candles (fc) 0 fc…39.99 kfc 0 fc…39.99 kfc from 0.001 fc from ±(2% m.v. + 5 digits)
Phase sequence indication in the same direction (correct), opposite direction (incorrect), UL-L voltage: 95 V…500 V (45 Hz…65 Hz)

“m.v.” – measured value

Sonel MPI-540 | Specifications – 3-phase power quality recorder

The device is designed to work with mains:

  • with nominal frequency 50/60 Hz
  • with nominal voltage: 64/110 V, 110/190 V, 115/200 V, 127/220 V, 220/380 V, 230/400 V, 240/415 V, 254/440 V, 290/500 V
  • DC networks

Supported systems:

  • single-phase
  • split-phase with common N
  • three-phase – WYE with and without N conductor
  • three-phase – Delta
Parameter Measuring range Max. resolution Accuracy
Alternating voltage (TRMS) 0.0…500 V 0.01% Unom ±0,5% Unom
Alternating current (TRMS) depending on clamp* 0.01% Inom ±2% m.v. if m.v. ≥ 10% Inom, ±2% Inom if m.v. < 10% Inom , (error does not account for clamp error)
Frequency 40.00…70.00 Hz 0.01 Hz ±0.05 Hz
Active, reactive, apparent and distortion power depending on configuration (transducers, clamps) 4 significant digits depending on configuration (transducers, clamps)
Active, reactive and apparent energy secondo la configurazione (sensori, pinze) 4 significant digits as power error
cosφ and power factor (PF) 0.00…1.00 0.01 ±0.03
Harmonics
Voltage as for alternating voltage True RMS as for alternating voltage True RMS ±5% m.v. if m.v. ≥ 3% Unom, ±0,15% Unom if m.v. < 3% Unom
Current as for alternating current True RMS as for alternating current True RMS ±0,5% m.v. if m.v. ≥ 10% Unom, ±0,5% Unom jeśli m.v. < 10% Unom
THD
Voltage 0.0…100.0% (relative to RMS value) 0.1% ±5%
Current 0.0…100.0% (relative to RMS value) 0.1% ±5%
Unbalance factor 0.0…10.0% 0.1% ±0.15% (absolute error)

*

  • F-1A, F-2A, F-3A clamp: 0…3000 A AC (10 000 Ap-p)
  • C-4A clamp: 0…1000 A AC (3600 Ap-p)
  • C-5A clamp: 0…1000 A AC/DC (3600 Ap-p)
  • C-6A clamp: 0..10 A AC (36 Ap-p)
  • C-7A clamp: 0…100 A AC (360 Ap-p)

Sonel MPI-540 | AC currentmeasurment (True RMS) with clamp

C-4A C-5A C-6A C-7A F-1A F-2A F-3A
Rated current 1000 A AC 1000 A AC
1400 A DC
10 A AC 100 A AC 3000 A AC 3000 A AC 3000 A AC
Frequency 30 Hz…10 kHz DC…5 kHz 40 Hz…10 kHz 40 Hz…1 kHz 40 Hz…10 kHz 40 Hz…10 kHz 40 Hz…10 kHz
Max. diameter of measured conductor 52 mm 39 mm 20 mm 24 mm 380 mm 250 mm 140 mm
Minimum accuracy ≤0,5% ≤1,5% ≤1% 0,5% 1% 1% 1%
Battery power
Lead length 2.2 m 2.2 m 2.2 m 3 m 2.5 m 2.5 m 2.5 m
Measurement category IV 300 V IV 300 V IV 300 V III 300 V IV 600 V IV 600 V IV 600 V
Ingress protection IP40 IP40 IP40 IP40 IP67 IP67 IP67

Sonel EVSE-01 | Functional comparison

MPI-540-PV MPI-540 MPI-535 MPI-530-IT MPI-530 MPI-525 MPI-520 MPI-507 MPI-506 MPI-502
auto measurements
automatic threephase measurement via multiplug
visual inspection
fault loop ZL-PE, ZL-N parameters measurement
6 mA RCD test
RCD test AC, A, F, B, B+, EV AC, A, F, B, B+ AC, A AC, A
insulation resistance RISO measurement
measurements report