Short circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
Measurment using 7,6/13,3 A current – Measurement range according to
IEC 61557: 0,13…1999 Ω
(for 1,2 m lead) and 0,19…1999 Ω (for WS-01 and WS-04).
Display range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(5% m.v. + 3 dgt) |
20,0…199,9 Ω | 0,1 Ω | |
200…1999 Ω | 1 Ω |
- Nominal work voltage: UnL-N/ UnL-L: 220/380 V, 230/400 V, 240/415 V,
- Voltage operating range: 100…264 V (for ZL-PE i ZL-N) and 100…440 V (for ZL-L),
- Nominal network frequency fn: 50 Hz, 60 Hz,
- Max. test current: 23 A (230 V), 44 A (440 V),
- PE terminal connection corectores check with the help of touch electrode
Readings of fault loop impedance R and fault loop reactance XL
Display range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(5% m.v. + 5 digits) of ZS value |
20,0…199,9 Ω | 0,1 Ω |
calculated and displayed for ZS<200 Ω.
Short circuit loop impedance ZL-PE in mode RCD – without RCD tripping
Measurement using <15 mA,current measurement range in accordance with IEC 61557: 0,51…1999,9 Ω
Display range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(6% m.v. + 10 dgt) |
20,0…199,9 Ω | 0,1 Ω | ±(6% m.v. + 5 dgt) |
200…1999 Ω | 1 Ω |
- test without tripping the RCD for IΔn ≥ 30 mA,
- nominal work voltage: Un: 220 V, 230 V, 240 V,
- voltage operating range:180…270 V,
- frequency operating range fn: 50 Hz, 60 Hz
- PE terminal connection correctness check with the help of touch electrode
Readings of fault loop impedance R and fault loop reactance XL (without tripping the RCD)
Display range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(6% m.v + 10 dgt) of ZS value |
20,0…199,9 Ω | 0,1 Ω | ±(6% m.v + 5 dgt) of ZS value |
- calculated and displayed for ZS<200 Ω.
RCD parameters test (voltage range 180…270 V):
RCD tripping test and measurment of tripping time tA (for tA function)
Breaker Type | Test Current Multiplier |
Range | Resolution | Accuracy |
Standard | 0,5*IΔn | 0…300 ms | 1 ms | ± (2% m.v. + 2 dgt) |
1*IΔn | ||||
2*IΔn | 0…150 ms | |||
5*IΔn | 0…40 ms | |||
Selective | 0,5*IΔn | 0…500 ms | ||
1*IΔn | ||||
2*IΔn | 0…200 ms | |||
5*IΔn | 0…150 ms |
- Precision of the differential current: 0,5*IΔn:-8…0% for 1*IΔn, 2*IΔn, 5*IΔn: 0…8%
Voltage measurement
Range | Range | Accuracy |
0,0 V…299,99 V | 0,1 V | ±(2% m.v. + 6 dgt) |
300 V…500 V | 1 V | ±(2% m.v + 2 dgt) |
Frequency measurement
Range | Range | Accuracy |
45,0 V…65,0 Hz | 0,1 Hz | ±(1% m.v. + 1 dgt) |
Touch voltage measurement referred to the rated residual current (UB)
Range | Resolution | Test Current |
Accuracy |
0..9,9 V | 0,1 V | 0,4 x IΔn | 10% m.v. ± 5 dgt |
10,0..99,9 V | 0…15% m.v. |
Measurementof the RCD disconection current IA for sine waveform testing current
Selected Current |
Range | Resolution | Test Current |
Accuracy |
10 mA | 3,3…10,0 mA | 0,1 mA | 0,3 x IΔn…1,0 x IΔn | ±5%IΔn |
30 mA | 9,0…30,0 mA | |||
100 mA | 33…100 mA | 1 mA | ||
300 mA | 90…300 mA | |||
500 mA | 150…500 mA |
- It is posible to start the measurement from the positive or negative half of the forced leaking current
RCD IA tripping current measurement for unidirectional pulsating residual current
Selected Current |
Range | Resolution | Test Current |
Accuracy |
10 mA | 4…20,0 mA | 0,1 mA | 0,35xIΔn..2,0xIΔn | ±10%IΔn |
30 mA | 12,0…42,0 mA | 0,35xIΔn..1,4xIΔn | ||
100 mA | 40,0…140 mA | 1 mA | ||
300 mA | 120…420 mA |
- Measurement is possible for a positive or negative forced leakage current.
Low voltage test of the circuit and insulation continuity
Measurement range in accordance with IEC61557:0,12…400 Ω
Test of PE wire continuity using a ±200 mA current
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(2% m.v + 3 dgt) |
20,0…199,9 Ω | 0,1 Ω | |
200…400 Ω | 1 Ω |
- Voltage on open terminals: 4…9 V,
- Test current at R<2 Ω: min. 200 mA,
- Autocalibration of test leads
- Measurements for both polarizations of the current
The device meets the requirements of EMC standards EN 61326 – 1:2006 and EN 61326 – 2-2:2006.
Electric safety:
- type of insulation: double, according to EN 61010 – 1 and IEC 61557
- measurement category: IV 300 V (III 600 V) according to EN 61010 – 1
- protection class acc. to EN 60529: IP67
Other technical data:
- dimentions: 220 x 98 x 58 mm
- weight: ~1 kg
- Auto OFF time: 300, 600, 900 second
- number of measurements Z and RCD (for NiMH batteries): >5000 (2 per minute)
„m.v.” measured value.