MPI-535

Catalog index: WMGBMPI535

Multi-Function Meter Of Electrical System Parameters

Keep up to date with products in the category

The MPI-535 meter is designed for checking home and industrial electrical installations. The measurements that can be made, by using the device, provides the results which determine the safety of the installation. The instrument allows to make a set of measurements of the parameters of protection against electric shock using a single universal device.

Significant automation of measurements of the meter makes possible to test functioning of residual current circuit breakers in the Auto mode, as well as in pre-programmed measuring sequences (so-called auto-tests), which can also be extended with own sequences. Automatic measurement of insulation resistance of 3-, 4- and 5-wire conductors is possible by using additional the AutoISO-1000C adapter.

Maximum functionality in a minimum price

  • The largest touch screen on the market (7”) – remarkable ergonomics and ease of use
  • Removable microSD memory card – easy increase of memory capacity
  • Li-Ion battery – longer operation of the meter
  • Measurement of all parameters related to earthing and protection against electric shock – one device instead of several
  • Quick measurement of the fault loop impedance in networks secured with RCD without triggering (up to several seconds) – time saver
  • Auto measurements – the ability to perform automatic measurements in sequence – simplified measurements
  • Fast path from measurements to report – time saver

Features

The meter offers a wide range of functionalities. It combines the measuring capabilities of several devices, while ensuring equally good accuracy.

MPI-535 can be used for all measurements for commissioning of electrical installations in accordance with applicable regulations:

  • short circuit loop impedance (also in circuits secured with RCDs),
  • RCD parameters,
  • insulation resistance,
  • earth resistance (4 measurement methods + soil resistivity measurement),
  • continuity of protective and equipotential bondings,
  • light intensity measurement,
  • phase sequence test,
  • motor rotation direction test.

Automatic installation safety test

MPI-535 allows safety control of residential, commercial and industrial electrical installations. Measurements can be easily automated with:

  • auto mode of residual current devices (RCD) tests,
  • auto measurements – freely configurable measuring sequences,
  • AutoISO-1000C adapter for automatic insulation resistance test of 3-, 4- and 5-conductor cables, without switching.

Ease of reading

The device is equipped with a color TFT LCD touch screen with a resolution of 800x480 pixels and a diagonal of 7”, which allows for convenient operation and easy reading of parameters and plotted waveforms. This screen size enables displaying more information, available at any time of use. The interface is visible in all conditions – also thanks to the appropriate size of displayed symbols. Included stylus allows to work also with dielectric gloves.

Built-in help system

The device has built-in help screens with measurement diagrams. Thanks to this you can easily and quickly check and make sure how to connect to a given system depending on the type of performed measurement.

Increased resistance to environmental conditions

The meter will cope well in difficult environmental conditions. Protection against penetration of dust and water is ensured by a unique housing with a level of protection IP51. It is resistant to mechanical damage, and a special design allows you to easily protect the touch screen by shielding using the cover of the meter. In addition to the fact that it protects against damage, it also allows you to conveniently carry and use the device in different positions.

Communication and software

A very strong feature of the device is the multitude of communication interfaces and cooperation with external software. You can easily transfer measurement data to your computer via USB port, removable SD memory card, or wireless communication (Bluetooth, Wi-Fi ).

In order to generate a report on measurements for electric shock protection, use Sonel Reports PLUS software. Saving the downloaded data to the simplest formats and printing is provided by free Sonel Reader software.

Specification

Fault loop impedance measurements:

  • impedance measurement with 23 A current (40 A for phase-to-phase voltage), max. resolution 0.001 Ω,
  • fault current-limiting resistor: 10 Ω,
  • range of measurement voltages: 95…440 V, frequencies 45…65 Hz,
  • fast (up to 5 s) fault loop impedance measurement with resolution up to 0.01 Ω in systems protected with RCDs not tripping at IΔn ≥ 30 mA,
  • automatic calculation of fault current on the basis of nominal or measured voltage; differentiation of phase-to-neutral and phase-to-phase voltage,
  • measurements using UNI-Schuko plug with measurement triggering button (including for swapped L and N leads) or 1.2 m, 5 m, 10 m, 20 m test leads, with optional use of three-phase socket adapters (AGT),
  • selection of installation protections and automatic evaluation of measurement results.

Testing of AC, A, F, B and B+ residual current devices:

  • measurement of general, short-time delay and selective RCDs with rated residual currents of 10, 30, 100, 300, 500 and 1000 mA,
  • function of automatic measurement of all RCD parameters (after pressing the “START” button once, the meter performs the entire defined cycle of measurements, including the capability of earth fault loop impedance measurement with 15 mA current),
  • shape of the input leakage current selected by the user: sinusoidal (start from rising or falling edge), unidirectional pulsating (positive or negative), unidirectional pulsating with direct current offset (positive or negative), constant (positive or negative),
  • measurement of tripping current IA with rising current,
  • measurement of tripping time tA with currents 0.5 IΔn, 1 IΔn, 2 IΔn and 5 IΔn,
  • measurement of touch voltage UB and protective conductor resistance RE without tripping the RCD,
  • detection of L and N phase swapping in a socket; does not affect measurements,
  • capability of measuring tripping current IA as well as actual tripping time tAI with just one RCD trip,
  • voltage measurements within the range of 95…270 V.

Measurement of insulation resistance:

  • measurement voltages: 50 V, 100 V, 250 V, 500 V, 1000 V,
  • measurement of insulation resistance up to 3 GΩ,
  • capability measurement in-socket by means of UNI-Schuko adapter,
  • sound signalling of five-second time intervals, facilitating capture of time characteristics,
  • meter protected against the presence of voltage on the object and the appearance of voltage during measurement,
  • automatic discharge of the measured object’s capacitance after completion of measurement,
  • automatic measurement of all resistance combinations of 3-, 4- and 5-core cords by means of the optional AutoISO-1000C adapter.

Earth resistance measurements:

  • according to 3- or 4-lead technical method with 2 auxiliary electrodes,
  • according to double-clamp method,
  • internal power source with frequency appropriate for 50 Hz or 60 Hz power network.

Soil resistivity measurements according to the Wenner method:

  • measuring range: 0.5 Ωm…9.99 kΩm,
  • distances between electrodes can be set in meters (1…30 m) or feet (1…90 ft).

Low-voltage continuity testing of protective conductors and equipotential bonding:

  • measuring range according to EN 61557-4: 0.12…400 Ω, max. resolution 0.01 Ω,
  • measurement of protective conductor continuity with current ≥200 mA in two directions,
  • low-current measurement with sound signalling,
  • voltage on open terminals: 4…9 V,
  • automatic calibration of test leads – leads of any length can be used.

Additional functions of the meter:

  • quick check of correct connection of PE conductor by means of contact electrode,
  • check of phase sequence and direction of motor rotation,
  • capability of charging from the power grid or 12 V car lighter socket,
  • tree-like memory structure with dynamic management,
  • data transmission to PC via USB.

Other technical specifications:

  • type of insulation – double, as per EN 61010-1 and EN 61557
  • power supply – Li-Ion rechargeable battery 11.1 V 3.4 Ah 37.7 Wh
  • operating temperature range 0…+50°C

The instrument meets the requirements set forth in the standards:

  • EN 61010-1 (general and particular requirements related to safety)
  • EN 61010-031 (general and particular requirements related to safety)
  • EN 61326 (electromagnetic compatibility)
  • EN 61557 (requirements for measurement instruments)
  • HD 60364-6 (performance of measurements – checking)
  • HD 60364-4-41 (performance of measurements – shock protection)
  • PN-PN-E 04700 (performance of measurements – commissioning tests)
  • EN 12464 (lighting workplaces)